15800
Description:
Fused disconnect switch for use only with the following fuses; Main: Telpower® TPS 3 to 70 Amp, Alarm: Cooper
Bussmann GMT-A only .
Recommend GMT-X Cover
Ratings:
Volts: 60Vdc
Amps: 3-70A
SCCR: 100kA
Agency Information: CE, UL Recognized, Guide QPQY2, File E97649.
Flammability Rating: UL 94V0, 150°C.
Features and Benefits
• Alarm output with wire wrap terminal or connection to 0.063” thick common alarm bus
• Spare alarm and power fuse compartment
• Mounting hardware included
Typical Applications:
• Telecommunications DC power circuit protection
Catalog Numbers
15800-R-200 Rear Access Panel Mounting
15800-F-200 Front Access Panel Mounting
Dimensions - in (mm)
15800-R-200
15800-F-200
General Information:
• For use with the following fuses only:
Main: Telpower® TPS 3 to 70 Amp
Alarm: Bussmann GMT-A only .
Recommend GMT-X Cover .
• Application Note: The line connection uses a 1/4 - 20 bolt that threads into the line terminal. The line terminal is designed with a float of ±.02 to allow for variation in the distance between the 15800 mounting flange and the line bus bar (see dimensional data). Equipment should be designed to eliminate any relative movement between the 15800 mounting flange and the line bus bar.
• Alarm output with wire wrap terminal or connection to .063” thick common alarm bus.
• Thermoplastic housing material U.L. rated 94V-0, 150°C.
• Spare alarm and power fuse compartment.
• Mounting hardware included.
Accessories
• Spare fuse holders: Catalog Numbers TPSFH-AS (for TPS fuses) and TPSFH-T (for GMT fuses).
总机: 0755-82862885, 82862629
传真: 总机 转 801
邮箱: service@bussmann.net.cn
网址: http://www.bussmann.net.cn
资料中心: http://www.bm-bussmann.com