cooper bussmann

Modular Fuse blocks for North American High Speed fuses

  
Catalog Symbol: 1BS101
Voltage Rating: 600V
Current Rating: 100A
Base: Molded black phenolic, 150°C
Mounting Studs: Zinc-plated steel; 1/4" - 20 x 1/2" hex head bolt
Nut: Zinc-plated steel
Washer: Zinc-plated steel; 1/4" Belleville washer
Connector: Tin-plated aluminum
Wire Range: Single #2/0 through single #14AWG
Wire Types: Copper or aluminum; Stranded or solid
Withstand Rating:
200,000A RMS. SYM. or the interrupting rating of the fuse used, whichever is smaller.
Dovetail Interlock:
Dovetail interlock feature on each side of the base allows mounting multiple poles adjacent to one another.
Torque Requirements:
Conductor Set Screw: 120 lbs-in
Fuse Mounting Bolt: 70 lbs-in
Agency Approvals:
U.L. Recognized, Guide No. IZLT2, File No. E14853; CSA Certified, Class 6225-01, File 47235

Mounting Dimensions mm (inches
Catalog No. “A” “B” “C”
FWA 70A-100A 49.3 (1.94) 16.0 (0.63) 95.4 (3.75)
FWH 35B-60B 58.9 (2.32) 25.6 (1.01) 104.9 (4.13)
FWH 70B-100B 72.4 (2.85) 39.1 (1.54) 118.3 (4.66)
FWX 35A-60A 59.4 (2.34) 26.1 (1.03) 105.4 (4.15)
FWX 70A-100A 59.7 (2.35) 26.4 (1.04) 105.6 (4.16)
KAC 1-30 63.5 (2.50) 30.2 (1.19) 109.4 (4.31)
KAC 35-60 88.9 (3.50) 55.6 (2.19) 134.8 (5.31)
KAC 70-100 105.7 (4.16) 72.3 (2.85) 151.6 (5.97)
KBC 35-60 88.9 (3.50) 55.6 (2.19) 134.8 (5.31)
KBC 70-100 93.0 (3.66) 59.6 (2.35) 138.9 (5.47)
LPJ 70SP-100SP 95.5 (3.76) 62.2 (2.45) 141.4 (5.57)
JJS 70-100 59.9 (2.36) 26.6 (1.05) 105.9 (4.17)
JKS 70-100 96.3 (3.79) 62.9 (2.48) 142.2 (5.60)
80-100L14C 89.9 (3.54) 56.6 (2.23) 135.8 (5.35)
80-100L09C 112.0 (4.41) 78.7 (3.10) 157.9 (6.22)

Dimensions



CATALOG SYMBOL: 1BS102
VOLTAGE RATING: 600V
CURRENT RATING: 400A
BASE: Molded black phenolic, 150°C
MOUNTING STUDS: Zinc-plated steel;1/4" - 20 x 1/2" hex head bolt
NUT: Zinc-plated steel
WASHER: Zinc-plated steel;1/4" Belleville washer
CONNECTOR: Tin-plated aluminum
WIRE RANGE: Single #6AWG through two 250MCM
WIRE TYPES: Copper or aluminum; Stranded or solid
AGENCY APPROVALS:
UL Recognized, Guide No. IZLT2, File No. E14853; CSA Certified, Class Pending

WITHSTAND RATING:
200,000A RMS. SYM. or the interrupting rating of the fuse used, whichever is smaller.

TORQUE REQUIREMENTS:
Conductor Set Screw: 275 lbs-in
Fuse Mounting Bolt: 120 lbs-in

Mounting Dimensions mm (inches)
Catalog No. “A” “B” “C”
FWA 70A-100A 50.3 (1.98) 8.9 (0.35) 167.9 (6.61)
FWH 125B-200B 70.4 (2.77) 29 (1.14) 188 (7.4)
FWX 125A-200A 61.2 (2.41) 19.8 (0.78) 178.8 (7.04)
KBC 110-200 94 (3.7) 52.6 (2.07) 211.6 (8.33)
70-100CJ 92.2 (3.63) 50.8 (2) 209.8 (8.26)
125-200M09C 111.3 (4.38) 69.9 (2.75) 228.9 (9.01)
250-400P09C* 111.3 (4.38) 69.9 (2.75) 228.9 (9.01)
JJS 110-200 63.5 (2.5) 22.1 (0.87) 181.1 (7.13)
*When used in multiple pole configurations, 19.05 (.750) should be maintained between adjacent moldings when mounting the fuses indicated.

Dimensions



Catalog Symbol: 1BS103
Voltage Rating: 600V
Current Rating: 400A
Base: Molded black phenolic, 150°C
Mounting Studs: Zinc-plated steel; 3/8" - 16 x 3/4" hex head bolt
Nut: Zinc-plated steel
Washer: Zinc-plated steel; 3/8" Belleville washer
Connector: Tin-plated aluminum
Wire Range: Single #6AWG through two 250MCM
Wire Types: Copper or aluminum; Stranded or solid
Withstand Rating:
200,000A RMS. SYM. or the interrupting rating of the fuse used, whichever is smaller.

Torque Requirements:
Conductor Set Screw: 275 lbs-in
Fuse Mounting Bolt: 170 lbs-in

Agency Approvals:
U.L. Recognized, Guide No. IZLT2, File No. E14853; CSA Certified, Class 6225-01, File 47235

Mounting Dimensions mm (inches)
Catalog No. “A” “B” “C”
FWH 225A-400A 83.8 (3.3) 42.4 (1.67) 201.4 (7.93)
FWX 225A-400A 67.6 (2.66) 26.2 (1.03) 185.2 (7.29)
KAC 110-200 109.2 (4.3) 67.8 (2.67) 226.8 (8.93)
KBC 225-400 103.1 (4.06) 61.7 (2.43) 220.7 (8.69)
160-400LMT 58.9 (2.32) 17.5 (0.69) 176.5 (6.95)
250-400P11C* 184.2 (7.25) 142.7 (5.62) 301.8 (11.88)
JJN 225-400 46.7 (1.84) 5.3 (0.21) 164.3 (6.47)
JJS 225-400 69.1 (2.72) 27.7 (1.09) 186.7 (7.35)
CGL 225-400* 184.2 (7.25) 142.7 (5.62) 301.8 (11.88)
*When used in multiple pole configurations, 25.40 (1.000) should be maintained between adjacent moldings when mounting the fuses indicated.

Dimensions


Catalog Symbol: 1BS104
Voltage Rating: 600V
Current Rating: 600A
Base: Molded black phenolic, 150°C
Mounting Studs:
Zinc-plated steel; 3/8" - 16 x 3/4" hex head bolt
Nut: Zinc-plated steel
Washer: Zinc-plated steel; 3/8" Belleville washer
Connector: Tin-plated aluminum
Wire Range: Single #4AWG through two 500MCM
Wire Types: Copper or aluminum; Stranded or solid
Withstand Rating:
200,000A RMS. SYM. or the interrupting rating of the fuse used, whichever is smaller.

Torque Requirements:
Conductor Set Screw: 375 lbs-in
Fuse Mounting Bolt: 170 lbs-in

Agency Approvals:
U.L. Recognized, Guide No. IZLT2, File No. E14853; CSA Certified, Class 6225-01, File 47235

Mounting Dimensions mm (inches)
Catalog No. “A” “B” “C”
FWA 500A - 600A 62 (2.44) 19.1 (0.75) 222.3 (8.75)
FWH 450A - 600A 74.7 (2.94) 31.8 (1.25) 235 (9.25)
FWX 450A - 600A 62.5 (2.46) 19.6 (0.77) 222.8 (8.77)
KAC 225 - 400 123.7 (4.87) 80.8 (3.18) 284 (11.18)
KAC 450 - 600 122.9 (4.84) 80 (3.15) 283.2 (11.15)
KBC 450 - 600 95 (3.74) 52.1 (2.05) 255.3 (10.05)
JJN 450 - 600 51.6 (2.03) 8.6 (0.34) 211.8 (8.34)
JJS 450 - 600 74.9 (2.95) 32 (1.26) 235.2 (9.26)
450 - 600R11C* 184.2 (7.25) 141.2 (5.56) 344.4 (13.56)
CGL 450 - 600* 184.2 (7.25) 141.2 (5.56) 344.4 (13.56)
*When used in multiple pole configurations, 12.70 (.500) should be maintained between adjacent moldings when mounting the fuses indicated.