cooper bussmann

Data Signal SPDs For Measurement, Control and Regulation Circuits, and Twisted Pairs

  

UL Listed 497B DIN-Rail Mount Universal Surge Protective Device for Measuring and Control Circuits, and Bus Systems

Description
The Cooper Bussmann universal four-pole, DIN-Rail mounted surge arresters provide effective protection with minimum space requirements and are designed for stringent requirements on the availability of measuring and control circuits, and bus systems.
To ensure safe operation, the arresters provide protection against vibration and shock up to a 30-fold acceleration of gravity. The function-optimized design of the devices allows quick and easy removal of protection modules via “make-before-break” terminals that assure continuity of data signals in the protected and unprotected state.

For IEC Applications - Instruction for Surge Protective Device Use In Zone 2 Explosive Atmospheres per ATEX.
1.When installed in potentially explosive atmospheres, the Data Signal DIN Series shall be installed into an enclosure which meets the requirements of a recognized type of protection, in accordance with EN 60079-0.
2. The Data Signal DIN Series as transient suppressor. This approval applies to the following equipment types:
• BSPD5DING
• BSPD12DING
• BSPD24DING
• BSPD48DING
• BSPD5DINLHF
• BSPD24DINLHF

Ambient and Temperature Class
• -40°C to +80°C, T4:
DEKRA 12ATEX0254 X: II 3 G Ex nA IIC T4 Gc
• Standards used for:
ATEX: EN60079-0: 2009, EN 60079-15: 2005
• UL 497B Listed
• Function-optimized design for safe use and easy installation
• Four-pole and base mounts on grounded 35mm DIN-Rail
• Module removal without signal interruption via "make-before-break" ceicuitry.
• 0-180V BSPD0180DINL automatically adjusts to system operating voltage and can protect data circuits of different voltages up to 100mA load current.

Dimensions-mm


Circuit Diagrams


TecHNIcAL DATA
catalog number  BSPD5DING BSPD12DING BSPD24DING BSPD48DING BSPD5DINLHF BSPD24DINLHF BSPD0180DINL
Nominal voltage (UN) 5V 12V 24V 48V 5V 24V 0-180V
Nominal current at 45°c (IL) 1.0A 0.75A 0.75A 0.75A 1.0A 1.0A ≤0.1A@80°c
VPL line-line for Iimp D1 (Up) ≤29V ≤50V ≤102V ≤160V ≤25V ≤65V ≤ UN + 53V
VPL line-PG for Iimp D1 (Up) ≤27V ≤37V ≤66V ≤95V ≤550V ≤550V -
VPL line-line at 1kV/µs c3 (Up) ≤18V ≤38V ≤90V ≤140V ≤11V ≤47V see Note 1
VPL line-PG at 1kV/µs c3 (Up) ≤9V ≤19V ≤45V ≤70V ≤550V ≤550V -
VPL line-line for In c2 (Up) - - - - - - see Note 2
VPL line-PG for c2 / c3 / D1 - - - - - - ≤ 550V
D1 Total lightning impulse current (10/350µs) (Iimp) 10kA 10kA 10kA 10kA 10kA 10kA 10kA
D1 Lightning impulse current (10/350µs) per line (Iimp) 2.5kA 2.5kA 2.5kA 2.5kA 2.5kA 2.5kA 2.5kA
c2 Total nominal discharge current (8/20µs) (In) 20kA 20kA 20kA 20kA 20kA 20kA 20kA
c2 Nominal discharge current (8/20µs) per line (In) 10kA 10kA 10kA 10kA 10kA 10kA 10kA
Series impedance per line 1.0Ω 1.8Ω 1.8Ω 1.8Ω 1.0Ω 1.0Ω 10Ω/7.5Ω typ
Frequency of the operating voltage (fUN) - - - - - - 0-400Hz
Max. continuous operating Dc voltage (Uc) 6V 15V 33V 54V 6V 33V 180V
Max. continuous operating Ac voltage (Uc) 4.2V 10.6V 23.3V 38.1V 4.2V 23.3V 127V
Permissible superimposed signal voltage (USignal)             ± 5V
"Nominal current at 80°c (IL)
(corresponds to max. short-circuit current)"
100mA
cut-off frequency line-PG (fG) 1.0MHz 2.7MHz 6.8MHz 8.7MHz 100MHz 100MHz -
cut-off frequency line-line (USignal, balanced 100Ω) (fG) - - - - - - 50MHz
capacitance line-line (c) ≤2.7nF ≤1.0nF ≤0.5nF ≤0.35nF ≤25pF ≤25pF ≤80pF
capacitance line-PG (c) ≤5.4nF ≤2.0nF ≤1.0nF ≤0.7nF ≤16pF ≤16pF ≤16pF
ATeX Approvals
Agency information †† †† †† †† †† ††
Iec 61643-21 Test category D1, c2, c3
Operating temperature range -40°c to +80°c
Degree of protection IP20
For mounting on 35mm DIN-Rails per eN 60715
Grounding Via base part
color / enclosure material Grey / Polyamide PA 6.6
Test standards Iec 61643-21 / eN 61643-21, UL 497B
connection (input / output) Screw terminal
conductors Solid 12-28AWG (4-0.08mm2)
Flexible 14-28AWG (2.5-0.08mm2)
Terminal torque 3.5 Lb-In (0.4 N•m)
Note 1 - See Diagram 1 - VPL line-line graph line C3.
Note 2 - See Diagram 1 - VPL line-line graph line C2.
† DEKRA 12ATEX0254 X: II 3 G Ex nA IIC T4 Gc
†† ATEX, UL, CSA
‡ UL 497B

0-180V SPD Application and Mode of Operation
The BSPD0180DINL surge protective device automatically adjusts to the operating voltage (from 0 to 180 volts) of the protected device.
When an overvoltage event occurs, the SPD voltage protection level adjusts itself based upon the output terminal operating voltage of the base.
Diagram 1: Voltage Protection Level Up (V) (Line - Line)



DIN-Rail Universal 4 Wire Data Signal SPDs and Applications
Universal 4 wire data signal SPD products are specified by communication technology. The table below contains the specific SPD product, by part number, and the applications to which they are suited to be used.

Part Numbers BSPD5DING BSPD12DING BSPD24DING BSPD48DING BSPD5DINLHF BSPD24DINLHF BSPD0180DINL
BUS SYSTEMS AND MEASURING, AND CONTROL TECHNOLOGY
0-20 mA, 4-20 mA Signals     X     X (4-20mA only) X
Binary Signals X X X X      
CAN-Bus (data line only)         X   X
C-Bus (Honeywell)         X   X
Data Highway Plus             X
Device Net (data line only)         X   X
Dupline             X
E-Bus (Honeywell)             X
Fieldbus Foundation           X X
FIPIO / FIPWAY           X  
FSK         X   X
IEC-Bus (RS485)         X   X
Interbus INLINE (I/O)             X
Interbus INLINE, Long-distance bus         X   X
K Bus           X  
LON - TP/XF 78         X    
LUXMATE Bus           X X
M Bus             X
MODBUS         X   X
MPI Bus         X   X
Procontic CS31 (RS232)   X          
Procontic T200 (RS422)         X   X
PROFIBUS DP/FMS         X   X
PROFIBUS PA           X X
PROFIBUS SIMATIC NET         X   X
PSM EG RS422 & RS485         X   X
Rackbus (RS485)         X   X
R Bus         X   X
RS 485         X   X
RS422, V11         X   X
SafetyBUS p         X   X
Securilan LON Bus         X    
SIGMASYS       X      
SS97 SIN/X (RS 232)   X          
SUCONET         X   X
Resistance Temp. Measuring Ni1000, PT100, PT1000 Wire NTC & PTC Thermistors   X          
TTL   X          
TTY 4–20mA     X        
TELECOMMUNICATION, TELEPHONY
a/b Wires             X
ADSL, ADSL 2+             X
ISDN S0, S2m/U2m, UKO/UPO             X
Modem M1   X          
SDSL, SHDSL           X X
Telephony Systems
(e.g., Siemens, HICOM, Alcatel)
            X
T-DSL             X
Telecommunication Systems
(e.g., Siemens, HICOM, Alcatel)
            X
VDSL             X
DATA NETWORKS
V 24 (RS232 C)   X          

 

----------------------------------