Product description
Eaton’s Bussmann series Red Spot range of offset bolted tags BS fuse links (in sizes A1 to A4) is specifically designed for the protection of general industrial applications, e.g. power distribution, cable protection, motor protection.
Features
• Good peak and let-through current limitation
• 1:1.6 Selective coordinate ratio between ‘minor’ and ‘major’ fuse
• Suitable for motor protection as gM ratings enhance the breaking capacity capability
• Power loss values well within the limits of IEC 60269
Standard/Agency information:
• BS88-2
• IEC 60269-2
Technical data:
• Breaking capacity: AC: ASTA 20 certified to 80 kA, generally at 660 Volts to BS88 part 2 1988 (IEC 60269-2)
• Minimum interrupting rating: 1.6 x In
Dimensions - mm
Time current curve
Catalog numbers | Rated voltage | Rated current (Amps) | BS Reference | Breaking capacity | Operating class |
I2t (A2s) Pre- arcing |
Total at rated voltage |
Fixing centre (mm) |
Pack quantity | Alternative fuse links | Compatible fuse holders |
NIT2 | 550 V a.c./ 250 V d.c. | 2 | A1 | 80 kA | gG | 2.2 | 15 | 44 | 20 | NITD | RS20 or CM32FC |
NIT4 | 4 | A1 | 80 kA | gG | 7.2 | 50 | |||||
NIT6 | 6 | A1 | 80 kA | gG | 22 | 150 | |||||
NIT10 | 10 | A1 | 80 kA | gG | 170 | 1000 | |||||
NIT16 | 16 | A1 | 80 kA | gG | 200 | 1350 | |||||
NIT20 | 20 | A1 | 80 kA | gG | 360 | 2200 |
Dimensions - mm
Time current curve
总机: 0755-82862885, 82862629