Description:
Fused and non-fused rainproof air conditioner pullout units.
Construction: NEMA 3R rainproof metal housing with weather resistant coating.
Wire Range: 14-3 AWG, Al/Cu
Ratings:
Phase: Single, 2-wire
Volts: 240Vac
Amps: 30-60A
Agency Information: UL Listed to UL 1429, C-UL Certified, UL Guide WGEW
Features and Benefits
• A/C disconnects meet NEC® Code Requirements under articles 440.14. GFCI units meet NEC® Code Requirements under articles 210.63, 210.8, and 406.8(B)(1).
• NEMA 3R rainproof enclosures withstand outdoor environment.
• Padlockable with two-position pullout handle to lock safety shield when in the ON position. (Not available on GF or NA units.) For added safety, pullout handle can be stored in the compartment in the off position.
Typical Applications
• Residential, light industrial/commercial A/C and heat pump service.
• Spas/whirlpools, swimming pools, pump houses
• Suitable for service entrance equipment applications with field installable ground bar, kit number DPFG.

Metallic Fused Disconnect

Metallic Non-Fused Disconnect

Metallic Non-Fused Disconnect with Weather Resistant- Tamper Resistant GFCI Receptacle.

B222-60NF34W non-fused with cable whip
Catalog Number | Description | Disconnect Rating | Max Hp Rating | Wire Range 60 or 75℃ CU/AL | Enclosure Type | Fuse Class | Approx. Dimensions(in) | |||
120V | 240V | Height | Width | Depth | ||||||
FUSED | ||||||||||
B221-30F | 30A, Pullout | 30A | 1.5 | 3 | #14-3 | NEMA 3R | H or R | 8 3/4 | 5 3/8 | 2 7/8 |
B221-30FGF | 30A, Pullout w/ GFCI | 13 | 7 1/2 | 4 3/4 | ||||||
B221-30FGFWRTR | 30A, Pullout W/ WRTR-Rated GFCI | |||||||||
B222-60F | 60A, Pullout | 60A | 3 | 10 | 8 3/4 | 5 3/8 | 2 7/8 | |||
B222-60FGF | 60A, Pullout w/ GFCI | 13 | 7 1/2 | 4 3/4 | ||||||
B221-60FGFWRTR | 60A, Pullout W/ WRTR-Rated GFCI | |||||||||
NON-FUSED | ||||||||||
B222-60NF | 60A, Pullout | 60A | 3 | 10 | #14-3 | NEMA 3R | * | 8 3/4 | 5 3/8 | 2 7/8 |
B222-60NFGF | 60A, Pullout w/ GFCI | 11 3/4 | 6 1/2 | 4 1/2 | ||||||
B222-60NFGFWRTR | 60A, Pullout W/ WRTR-Rated GFCI | |||||||||
B222-60NFNA | 60A, Switch | * | 8 3/4 | 5 3/8 | 3 5/8 | |||||
NON-FUSED CABLE WHIP | ||||||||||
B222-60NF12W | 60A, Pullout w/ 1/2" Cable Whip | 60A* | 3 | 10 | #14-3 | NEMA 3R | * | 14 3/4 | 12 1/2 | 4 |
B222-60NF34W | 60A, Pullout w/ 3/4" Cable Whip | 60A** |
Cable Whip Specifications
Catalog Numbers | Description | Pullout Rating | Max UpstreamWire Overcurrent Protection Device | Harness Diameter | Ground Hot Wire Size | Flexible Wire Size | Conduit Length (ft) | Non-Metallic Fittings |
B222-60NF12W | 60A, Pullout w/ 1.2" Cable Whip | 60A | 30A | 1.2" | #10 | #10 | 6 | 1 - 90°, 1 - Straight |
B222-60NF34W | 60A, Pullout w/ 3.4" Cable Whip | 60A | 50A | 3.4" | #8 | #10 | 6 | 1 - 90°, 1 - Straight |
* Upstream overcurrent protection device (OCPD) not to exceed 30 Amps.
**Upstream overcurrent protection device (OCPD) not to exceed 50 Amps.
30 and 60A pullout replacement handle: 96-3258-4.