Description:
High speed fuses for the protection of DC circuits in equipment.
High speed fuses for the protection of DC circuits in equipment.
Ratings:
Volts: 4000Vdc
Amps: 20-450A
IR: 60kA L/R: 25 ms.
Agency Information: Consult Cooper Bussmann.
Electrical Characteristics
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage Eg.
Peak Let-Through Curve
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
Catalog Numbers
Dimensions (mm):
Type 1*SKN/394
Type 2SKN/394
Type 2//SKN/394
Catalog Numbers
Fuse Type | Cat Numbers | Electrical Characteristics | ||
-SKN/394 Type K Indicator |
Rated Voltage (Vdc) |
Rated Current RMS-Amp |
Watts Loss (W) |
|
1*SKN/394 |
170E3914 170E3915 170E3916 170E3917 170E3918 170E3919 170E3984 170E3933 170E3922 |
4000 |
20 25 32 40 50 63 80 100 125 |
23 28 34 45 57 72 91 114 143 |
2 SKN/394 |
170E8882 170E8883 170E8884 |
160 200 250 |
182 228 285 |
|
2//2SKN/394 |
170E8885 170E8886 170E8887 170E8888 |
315 350 400 450 |
360 400 455 515 |
Dimensions (mm):
Type 1*SKN/394
Type 2SKN/394
Type 2//SKN/394
Square Body DC Fuses — 20-125A: 2000V
Time-Current Curve
Square Body DC Fuses — 160-450A: 4000V
Time-Current Curve
Square Body DC Fuses — 20-125A: 2000V
Peak Let-Through Curve
Square Body DC Fuses — 160-450A: 4000V