cooper bussmann

170M Square Body DIN 43620-690V(IEC/UL):10-315A

  
Specifications
Square body DIN 43 620 blade style high speed fuses.
Volts: 690Vac
Amps: 10-315A
IR: 200kA RMS Sym.
Agency information: CE, Designed and tested to IEC 60269: Part 4, UL Recognized.

Electrical Characteristics
Total Clearing I2t

The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics.
For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).

Arc Voltage

This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor
of 15%.

Power Losses

Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.

Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters

Dimensions (mm)


Catalog Numbers
DIN Type T Indicator for Micro Size Electrical Characteristics
Rated Current RMS-Amps I2t(A2 Sec) Watts Loss
Pre-arc Clearing at 660V
170M1558D 000 10A 4 27 2.5
170M1559D 16A 7 51 4
170M1560D 20A 11.5 82.5 5
170M1561D 25A 19 140 6
170M1562D 32A 40 285 7
170M1563D 40A 65 490 8.5
170M1564D 50A 115 815 9.5
170M1565D 63A 215 1550 11.5
170M1566D 80A 380 2700 15
170M1567D 100A 695 4950 16.5
170M1568D 125A 1180 8250 21.5
170M1569D 160A 2300 16500 25
170M1570D 200A 4350 31000 29.5
170M1571D 250A 7900 56000 35.5
170M1572D 00 315A 12000 84500 45
• Watts loss provided at rated current.
• Microswitch indicator ordered separately. See accessories on pages 185-186. Rated Current

The rated current of this fuse range has been given with copper conductors that have a current density of 1.3 A/mm2 (IEC 60269-4). For conductor cross section according to IEC 60269-1, the fuses with a rated current higher than 125A must be derated.

Size 000 — 10-315A: 690V
Time-Current Curve


Peak Let-Through Curve
----------------------------------
伊顿 EATON BUSSMANN 规格资料查询
伊顿 EATON BUSSMANN 规格类型
或许您会感兴趣...
联系客服
深圳市博孚美科电子有限公司
总机: 0755-82862885, 82862629
传真: 总机 转 801
邮箱: service@bussmann.net.cn
网址: http://www.bussmann.net.cn